Frequency measurement device MIDAS FMD2
  • Карта проектов. Выполнено по всему миру 1000 проектов

  

Reference list

Frequency measurement device MIDAS FMD2

Frequency measurement device MIDAS FMD2

1.1.    Device assignment

MIDAS FMD2 is designed to measure the pulse frequency, calculate the speed of rotation and acceleration of rotation, generate alarm, warning and other signals based on the measured and calculated value processing and transmit received information on the upper level computing device (hereinafter - ULCD). The personal computer, smart controller or another device which satisfies arrangements outlined in this manual.

MIDAS FMD2 primarily intended for use in the electronic part of the steam and hydraulic turbine control and protection systems.

MIDAS FMD2 is interchangeable, restoreable, repairable, four channel and multi-functional product and It refers to the measuring equipment that can be tested, used in stationary conditions of production facilities outside the houses.

MIDAS FMD2 refers to the combined measurement device with galvanic decoupler, which has both digital and discrete outputs.

MIDAS FMD2 manufactured in accordance with technical conditions (hereinafter – TC)  4252-006-27462912-08.

Due to continuous product improvement there may be minor changes to the circuitry and design, which doesn’t affect its functionality and performance specification.

1.2. Features
  • Indicators 
    – Four independent channels for frequency measurement;
    – a wide range of measured frequency: from 0.04 to 20000 Hz;
    – a wide range of input signal amplitudes: from 4 to 24 V;
    – input pulse shape independency: rectangular, triangular, sine;
    – the minimum duration of the input pulse of either polarity: 5 ms;
    – fill-in frequency used for high resolution measurement of the input pulse length: 72 MHz;
    – the basic error limits of frequency measurement;
         ±0,001% (reduced, in a range from 0.04 Hz to 100 incl.);
         ±0,002% (relative, in a range from 100 Hz to 1 KHz incl.);
         ±0,01 (relative, in a range from 1 to 3 KHz incl.);
         ±0,02 (relative, in a range from 3 to 10 KHz incl.);
         ±0,06 (relative, in a range from 10 to 20 KHz incl.);
    – the dielectric strength of the galvanic isolation between all channels of measurement, all interfaces RS422 and power supply circuits: 1000 V;
    – power consumption: not more than 10 W; – Operating temperature range: 0 to 60 ° C;
    – small size of module: not more than 109x115x46 mm. ·

  • Application examples:
    – as part of the electronic speed control systems of rotation of steam, gas and hydraulic turbines;
    – as an independent means of 3rd and 4th overspeed protection stages of hydraulic turbines;
    – as part of a fault protection system of steam and gas turbines with four independent frequency measurement channels;
    – as a means of determining the pumped-storage stations rotation direction (pump-turbines);
    – as a control signal generating device in the process of power systems automation (On / off pumps, brakes, drive, etc.);
    – as a channel of pulse frequency measurement in the automatic control systems. 
  • Built-in functions: – Various calculation based on measured values of frequency, rotational speed and acceleration for each channel independently;
    – configuring a wide selection of constant settings and range limits for continuous monitoring of 8 measured and calculated values;
    – the forming wide range of digital signals (hereinafter – DS) for each of the 8 controlled variables;
    – Configuring hysteresis during the registration of set point values transitions and ranges of the border separately for each of the 8 controllable variables;
    – configurable functions of motion control “Stop” and “Zero of speed”;
    – configurable function of the critical acceleration calculation for overspeed protection;
    – determining the direction of rotation by frequency phase outpacing of two measurement channels;
    – separate configuration of on and off condition for each output type of “open collector” on any DC. · 
  • Output interfaces:
    – Two independent galvanic isolated RS-422 interfaces for communication with ULCD;
    – four fixed exchange rates for each interface separately: 38400, 57600,115200, 230400 bit/s;
    – isolated RS-422 interface for output to sign synthesis indicators CCD CD-RS422-PM-07;
    – 8 built-in discrete outputs with a maximum sustained load current of 0.5 A and voltage up to 30 V
1.3. Specifications Table. 1 
         – MIDAS FMD2 technical characteristics

Group

Parameter name

Value

Units

Input

interface

1

The number of functionally independent measurement channels

4

 

2

Number of measuring inputs for each channel

2

 

Low voltage input  L

from 4 to 10

V

High voltage input H

from 10 to 24

V

3

Input impedance at least:

 

 

Input L

500

Ohm

input H

1500

Ohm

4

Input current no more than:

 

 

Input L

21

mА

Input H

21

mА

5

Channel zone-amplitude insensibility  no more than:

 

 

Input L

from 1 to 3

V

Input  H

from 2 to 4

V

6

The perceived shape of the input signal:

 

 

Sinwave signal

positive polarity

 

Rectangular voltage pulses

positive polarity

 

voltage pulses of triangular shape

positive polarity

 

Metrology

7

The range of measured frequency

from 0,04 to 20000

Hz

8

Output frequency measurement accuracy no more than:

 

 

 

reduced, in the range from 0.04 Hz to 100 Hz inclusive

± 0,001

%

relative, in the frequency range of 100 Hz to 1 kHz inclusive

± 0,002

%

relative, in the frequency range of 1 kHz to 3kHz inclusive

± 0,01

%

relative, in the frequency range of 3 kHz to 3kHz inclusive

± 0,02

%

relative, in the frequency range of 10 kHz to 20 kHz inclusive

± 0,06

%

The coefficient of thermal drift of the frequency measurement in the temperature range from 0 to 15 ° C and from 25 to 60 ° C, no more than:

 

 

in the frequency range from 0.04 Hz to 100 Hz inclusive

± 0,000033

%/°С

in the frequency range of 100 Hz to 1 kHz inclusive

± 0,00004

    %/°С

in the frequency range of 1 kHz to 3kHz inclusive

± 0,0002

    %/°С

in the frequency range of 3 kHz to 3kHz inclusive

± 0,0004

    %/°С

in the frequency range of 10 kHz to 20 kHz inclusive

± 0,0012

    %/°С

The minimum duration of the perceived pulse

5

mcsec

Measuring and calculating cycle:

 

 

when the input signal frequency> 100 Hz

10

msec

9

when the input signal frequency< 100 Hz

equal to the period of the input signal

 

Supply voltage

from 21,6 to 26,4

V

Power consumption, no more than:

10

Vat

10

Number of independent interface ports

3

 

11

The exchange rate of a number

38400, 57600, 115200, 230400

bit/sec

Interface specification

8 bits of data,
1 start-bit,
1 stop-bit,
no parity

 

Protocol Specification

MODBUS RTU

 

Power

supply

12

The number of installed nodes in the network

from 1 to 247

 

13

The maximum response time for a request

3

msec

RS422

14

The maximum length of the RS-422 communication line at a speed of:

 

 

15

38400 bit/sec

1200

m

16

57600 bit/sec

800

m

17

115200 bit/sec

400

m

18

230400 bit/sec

200

m

19

Number of digital outputs

8

 

20

The type of digital output

free collector

 

Maximum switching current

0,5

А

DC switching voltage, no more than

30

V

Binding response to events

free

programmable

for DS

 

Pulse repetition rate

measurand

Hz

Digital

outputs

21

Rotational speed

Rotational

Calculated

 Value

rev/min

22

Rotational acceleration

Calculated

 Value

rev/min/

sec

23

The presence of lead in phase (the direction of rotation or movement determination)

Digital signal (hereinafter – DS)

 

24

 

Input level high / low

DS

 

25

Zero speed

DS

 

Measurable and calculated value,
DS

26

Stop

DS

 

27

The presence of a critical acceleration (overspeed protection)

DS

 

28

Exceeding  the setting upper warning set point (hereinafter – UWS)  up

DS

 

29

Exceeding  the UWS down

DS

 

30

Exceeding  the setting lower warning set point (hereinafter – LWS) up

DS

 

31

Exceeding the LWS down

DS

 

32

Exceeding the upper alarm set point (hereinafter – UAS) up

DS

 

33

Exceeding the UAS down

DS

 

34

Exceeding the lower alarm set (hereinafter – LAS)  point up

DS

 

35

Exceeding the LAS down

DS

 

36

Finding the outside warning settings

DS

 

37

Finding the outside alarm settings

DS

 

38

Being outside of the acceptable settings

DS

 

39

Finding under the UWS

DS

 

40

Finding over the UWS

DS

 

41

Finding under the LWS

DS

 

42

Finding over the LWS

DS

 

43

Finding under the UAS

DS

 

44

Finding over the UAS

DS

 

45

Finding under the LAS

DS

 

46

Finding over the LAS

DS

 

47

Finding under the upper range level (hereinafter – URL)

DS

 

48

Finding over the URL

DS

 

49

Finding under the lower range level (hereinafter – LRL)

DS

 

50

Finding over the LRL

DS

 

51

Minimum pulse duration of perceptual module

from 5 to 255

mcsec

52

Quantity of impulses per one rotation

from 1 to 255

 

53

The settings for each channel, for each measured and calculated value:

 

 

 

54

URL

MAX

 

55

UAS

< URL

 

56

UWS

< UAS

 

Configurable

 user

settings

57

LWS

< UWS

 

58

LAS

< LWS

 

59

 

LRL

MIN

 

The the hysteresis settings magnitude of DS

> 0

 

The setting value of "Zero speed"

from LRL to URL

 

Options of overspeed protection:

 

 

Critical time

from 0 to 65535

ms

Critical speed

from 0 to 65535

rev/min

Dimensions

109х115х46

mm

60

Mounting on DIN-rail

there’s

 

61

Weight, no more than

350

g

62

Protection degree of the case in accordance with GOST 14254-96

IP20

 

Mechanical stress sustainability group in accordance with GOST 22261-94

5

 

Group of climatic conditions in the operation in accordance with GOST 22261-94

3

 

Design

63

Operating temperature range

from 0 to +60

°С

64

Storage temperature range

from -40 to +85

°С

65

Relative humidity range

from 10 to 80

%

66

The dielectric strength of the insulation between the inputs / interfaces of RS-422, and power, peak value for 60 seconds, at least

1000

V

Reliability

67

Estimated time of mean time to first failure for MIL-HDBK-217F under normal operating conditions, not less than

100000

hours

668

The average service life, not less than

12

years

      EMC

69

Functionality during exposing  of electromagnetic interference

Performance group III of ГОСТ 50746-2000

 

The level of the radiated interference

class А of ГОСТ Р 51318.22-99

 

Certifications

770

Certificate of Compliance organization's QMS(Quality Management System) requirements of ISO 9001: 2008

№Q-15.02.12d

 

71

Certificate of compliance with regulatory requirements

РОСС RU.АГ51.Н00029 №0744401

 

72

Certificate of type approval of measuring instruments

RU.C.33.022.A №38827

 

73

Permission to use

№РРС 00-048064

 

 

1.4.    Сonstruction

MIDAS FMD2 is a finish twinboard product, which is placed in the PHOENIX Contact ME MAX 45 5-3 case for mounting on mounting rail(DIN –rail). There are 40 screw terminals “for a clip” in the upper part of case for connecting external circuits. Each group is a detachable connection to simplify the installation. These groups allow pre-connect wires to the detachable part or make the connection to directly the module with detachable joins. Each group of terminals provided with a unique mechanical keys which do not allow the installation of the terminal group in the wrong position.

Appearance of MIDAS FMD2 which is mounted on a DIN - rail is show in the figure(Figure 1). Dimensional drawing of MIDAS FMD2 is shown in the figure (Figure 2). Configuration and Description of MIDAS FMD2 terminals shown in the table (Table 2).

Figure 1 - The appearance of MIDAS FMD2. Figure 2 - Overall drawing of MIDAS FMD2.

Table 2 - Configuration and description of MIDAS FMD2 terminals

of terminal

Designation

Type

Description

1

F IN 1 H +

Input

Frequency measurement Input 1 Н +

2

F IN 2 H +

Input

 Frequency measurement Input 2 Н +

3

F IN 3 H +

Input

Frequency measurement Input 3 Н +

4

F IN 4 H +

Input

Frequency measurement Input 4 Н +

5

DOUT 1

Output

Digital input 1

6

DOUT 2

Output

Digital input 2

7

DOUT 3

Output

Digital input 3

8

DOUT 4

Output

Digital input 4

9

F IN 1 L +

Input

Frequency measurement Input 1 L +

10

F IN 2 L +

Input

Frequency measurement Input 2 L +

11

F IN 3 L +

Input

Frequency measurement Input 3 L +

12

F IN 4 L +

Input

Frequency measurement Input 4 L +

13

DOUT 5

Output

Digital input 5

14

DOUT 6

Output

Digital input 6

15

DOUT 7

Output

Digital input 7

16

DOUT 8

Output

Digital input 8

17

F IN 1 -

Input

Frequency measurement Input 1 -

18

F IN 2 -

Input

Frequency measurement Input 2 -

19

F IN 3 -

Input

Frequency measurement Input 3 -

20

F IN 4 -

Input

Frequency measurement Input 4 -

21

+24VFOUT

Output

Voltage output

22

NC

-

Not used

23

NC

-

Not used

24

-24OUT

Output

Voltage output

25

A1 (RX+)

Input

RS 422 interface №1

26

B1 (RX-)

Input

27

Z1 (TX-)

Output

28

Y1 (TX+)

Output

29

A0 (RX+)

Input

RS 422 interface №0

30

B0 (RX-)

Input

31

Z0 (TX-)

Output

32

Y0 (TX+)

Output

33

NC

-

Not used

34

+24V

Input

Supply voltage

35

-24V

Input

Supply voltage

36

NC

-

Not used

37

A2 (RX+)

Input

RS 422 interface №0

38

B2 (RX-)

Input

39

Z2 (TX-)

Output

40

Y2 (TX+)

Output

 

1.5 Front panel


The upper surface of MIDAS FMD2 is a front panel is divided into two sections. Each section is closed by separate transparent protective plastic cover. The switches on the front panel can be accessed in the open position of the lid, visual inspection of switches regulations and and LEDs emission can be accessed in the close position. The upper surface of MIDAS FMD2 appearance presented under (Figure 3).

The control LEDs are located in both sections of the MIDAS FMD2 front panel. Eight yellow LEDs glow of «DIGITAL OUTPUT» are located in the left section from «1» to «8». These LEDs indicate the ON (active) state of the corresponding digital outputs.

Constant light of «PWR» LED in the right section indicates ON state of MIDAS FMD2. Three yellow LEDs «TX0», «TX1» and «TX2» in the right section indicate issuance of data from MIDAS FMD2 to ULCD by the respective interface.

The rhythmic flashing of green LED «RUN» reports about serviceability and cyclical working of microcomputers MIDAS FMD2 internal program.

In addition to the control LEDs on the MIDAS FMD2 front panel rotary switches are located on the 16th position. There are two groups of two rotary 16-position switches, which are marked «UNIT0» and «UNIT1».  They are intended for installation of the network node number for the corresponding RS422 interfaces. The node number is set in hexadecimal format. For example, to set the decimal number "10" of site it is necessary to set to "0" left switch in the group, and to set the right - in the «A» position. Setting range of the node number in the network is in the limit from 1 to 247. MIDAS FMD2 enters lock mode, when the node number set on the rotary switches. Out of range will occur automatically when you install a valid node number. 

One of the four possible exchange speeds with ULCD is set by rotary switch «SPEED». The exchange takes place via interfaces RS 422.0 b RS422.1. Compliance with the provisions of the exchange rate set by the switches shown in the table (Table 3.3).

Figure 3 - The appearance of the front surface of the MIDAS FMD2


2. Functional structure

Functionally MIDAS FMD2 is based on micro-computers STM32F103VDT. The MIDAS FMD2 structure includes:

  • input interface, which ensure the coordination and galvanic isolation of input signals; 
  • output interface, which is three independent galvanically isolated from the other circuits of the module bus driver RS422 interface; 
  • 8 microcomputer-controlled digital outputs, type of "open collector"; 
  • a secondary power source, providing the conversion of the supply voltage to a necessary voltage for MIDAS FMD2.

     3. Ordering Information
MIDAS FMD2 available in the following versions:
  • MIDAS FMD2 - powered by a DC supply of 24 V.
The MIDAS FMD2 Package Includes:
  • universal frequency meter MIDAS FMD2 - 1 pc .; 
  • Passport - 1 pc .; 
  • Electronic versions of this operating manual RAKURS.KB2.02.10.00RE with the procedure of checking MIDAS FMD2 and utility software - 1 pcs .; 
  • calibration interface cable (RAKURS.KB 2.01.40.00) - 1 pcs .;